cikkek ebben a kategóriában IEC 61850 and SPA bus communication at the same time We would like tu use IEC 61850 communication and also SPA bus at the same time. Do you have any solution for this kind of combination? The solution is the CPU+/1301 module. One port Ethernet and seri... No measurement values are being transmitted to the SCADA system In order to transmit on-line measurement values from the protection device to the SCADA system, the Line Measurement function block shall be active and its parameters shall be properly set. A ... A mérések nem továbbítódnak a SCADA felé IEC 61850 communication is not working If you have communication problems with IEC 61850, please check first the following common reasons: 1) The IED name must be different than TEMPLATE and it must start with an alphabetic character; num... IEC 61850 kommunikáció nem működik Changing setting groups in EP+ devices, adding new setting groups There are several ways to change between setting groups in EuroProt+ devices. Attached is a short summary, how the different channels can be used. Váltás a paraméter készletek között, új paraméter készlet felvétele Az EP+ készülékek különböző lehetőségeket kínálnak a paraméter készletek közötti átváltásra. A csato... EuroProt+ device RSTP support Can the EuroProt+ devices applied in RSTP-networks? EuroProt+ IEDs are allowed to connect to RSTP capable switches however IEDs are not processing RSTP management frames just simply let them through v...